One of three main
level
operating menus. From the PROGRAM menu, you can enter or
view step type, program loops, wait for conditions, set points, auxiliary (event) outputs
ON/OFF, and step duration.
Represents the current SYSTEM file of the Series 920 to be edited or reviewed.
Range: 1 to 10 files
Default: 1
Represents the current step of a file of the Series 920 to be edited or reviewed.
Range: 1 to 99 steps
Default: 1
One of six step types under the PROGRAM menu of the Series 920.
Can be pro-
grammed as a file or a
step to achieve or maintain a set point.
Represents the temperature that the system will try to achieve in the amount of time
given. This will be done linearly, producing a ramp from a beginning set point to an end
set point. In the RUN mode the SE prompt will appear. This represents the set
endpoint that the Series 920 is to achieve.
Range: RAL to RAH
Default: Unprogrammed
The number of hours, in combination with the
MIN
and SEC parameters, that
equal the total step time to achieve the temperature under the
SETPOINT
step-type.
This parameter
only
appears if PRG
-
TlME
under the SPCLFUNC menu.
Range: 0 to 23 hours
Default: Unprogrammed
The number of minutes that equal total
step time to achieve the temperature of the
Series 920.
Under the
SETPOINT
step-type. This parameter only appears if PRG
TIME under the SPCLFUNC menu.
Range: 0 to 59 minutes
Default: Unprogrammed
The number of seconds that equal total step time to achieve the temperature of the
Series 920. Under
the
SEtPOINT
steptype.
This parameter only appears if PRG
-
TIME under the SPCLFUNC menu.
Range: 0 to 59 seconds
Default: Unprogrammed
Represents the rate at which the set point changes in a given time. This parameter only
appears if PRG
=
RATE.
Range: 0.0
-
360.0°F10.0
-
200.0°C
minimum per minute
Default: Unprogrammed
This auxiliary output
oan
be an alarm or event.
EV1
only appears when
AUX1
=
EV.
Auxiliary outputs can be alarms or events.
Range: OFF or ON
Default: Unprogrammed
This auxiliary output can be an alarm or event.
EV2 only appears when
AUX2
=
EV.
Auxiliary outputs can be alarms or events.
Range: OFF or
ON
Default:
Unprogrammed
From RETURN, you can go back to SYSTEM prompt by pressing the ENTER key, or
return
to FILE? by pressing the MODE key.
One of six step types under the PROGRAM menu of the Series 920 that can be
programmed as a step or file.
You can jump from one step to anothr within a file.
The Series 920 will jump step to any step within your
current
file.
You cannot jump loop
to another step in another file.
Range: 1 to 99
Default
1
How To
Program
the Series
920,
Chapter 6
WATLOW
Series
920 User’s
Manual
51