The heating cycle time usually expressed in seconds for a
controller
to
complete
one ON/
OFF cycle. Time between successive turn ons. This parameter will not appear if: OUT
=
CL, or PB H
=
0 or if your Series 920 has a
4-2OmA
output and OUT
=
HT
or
HT/CL.
Range: 1 to 60 seconds
Default:
5
A thermal control band for heating, that defines where the rate
(derivative)
function begins.
This band is in multiples of the heat
proportional
band. This parameter
will
not appear if
OUT=CL, or PB H=0.
Range: 0 to 7 times PB H
Default: 0
The area where no heating or cooling takes
place
in a heat/cool proportional control. Not
displayed if OUT = HT or CL.
Range: -20 to
2O°F,
C or Units
Default: 0
A temperature band expressed in degrees
within
which a
temperature
controller proportion-
ing function is active for cooling. This parameter will not appear if OUT
=
HT.
Range: 0 to
900°F/0
to
500°C
Default:
45°F/25°C
Reset (integral) cooling control action that automatically eliminates offset, or “droop”,
between set point and actual process temperature in a proportional
control.
Expressed in
repeats per minute. This parameter will not appear if OUT
=
HT,
of
PB
C
=
0.
Range: 0.00 to 5.00 repeats/minute
Default
0.00
The rate
(derivative)
cooling function of the
Series
920. The rate is
determined
by how fast
the
error
being corrected is increasing.
Expressed in minutes. This parameter will not
appear if OUT=HT, or PB C=O.
Range: 0.00 to 5.00 minutes
Defauk
0.00
The cooling cycle time
expressed in
seconds for a controller to
complete
one ON/OFF
cycle. Time between successive turn ons. This parameter will not appear if: OUT
=
HT.
or
PB C
=
0. Your
Series
920 has a
4-20mA
output and OUT
=
CL or
CL/HT.
Range: 1 to 60 seconds
Default: 5
A thermal control band for cooling that defines where the rate
(derivative)
function begins.
Use the same as RB H. This band is in
multipIes
of the cool proportional band. This
parameter will not appear if OUT= CL, or PB C
=
0.
Range: 0 to 7 times PB C
Default: 0
From RETURN, you can go back to the SYSTEM prompt by pressing
the
ENTER key, or
return to
PID
by pressing the MODE key.
In the SETUP menu, ACCESS (3) must be selected
to enter
the MANUAL parameters.
Here you can manually adjust percent power.
When ACCESS (3) is selected under the SETUP mode of the Series 920, the MANUAL
parameters appear. The outputs revert to manual percent power control at the percent
of
power that they happen to be currently at.
Allows the operator to manually adjust the percent power output. The default value dis-
played and controlling at, is the value the
PID
calculated when the MANUAL parameter
menu was entered. -100 to 100 represents full
cool
to full heat,
respectively
This parame-
ter will take priority over the LOPWR and
HIPWR
parameters.
Range: -100 to 100
Default:
%
of power output when MANUAL is entered
46 WATLOW
Series 920