6.
Press the MODE key until the HOF
XX.XX
parameter appears on the
alphanumeric display. (The decimal point will not appear on the display of
your control.)
Use the UP/DOWN keys to adjust the alphanumeric dis-
play on the 920 to match the reading on the DVM. Once the two readings
match, press the ENTER key.
7.
Press the MODE key until ATZ
XXXX
appears on the alphanumeric
display. Set the precision decade box to the correct LOW setting from
Table 12 that corresponds to the type of 920 unit you have. Allow 10 sec-
onds for the unit to stabilize and then press the ENTER key.
8.
Press the MODE key until ATG
XXXX
appears on the lower display. Set
the precision decade box to the correct HIGH setting from Table 12 that
corresponds to the type of 920 that you have. Allow 10 seconds to stabi-
lize and then press the ENTER key. The unit is now calibrated for
RTD.
9.
Remove power from the Series 920. Remove wires from
l
,
#2,
and
#3.
Set DIP Switch
#8
to the OFF
position.
J
NOTE:
For
a
DIN curve
RTD, enter
the
SPCLFUNC menu
and use the
MODE
key to advance to
the RTD parameter.
Select
DIN.
Table 12
-
RTD
Calibration
Settings
for
JIS
WATLOW
Series
920 User’s
Manual 65