RETURN
1
Determines whether the alarm type for Auxiliary Output
1
will be a process
alarm
or a deviation
alarm for the Series
920.
This parameter will not appear if
AUX1
=
AL, or DIP switch
#7
is ON.
Range:
Alpha
Display
Alarm Type
Default: P
ALTYP1
P
Process Alarm
ALTYP1
D
Deviation Alarm
Determines whether the alarm type for Auxiliary Output 2 will be a process
alarm
or deviation
alarm. This parameter will not appear if AUX2
=
AL, or DIP switch
#7
is ON.
Range:
Alpha
Display
Alm
Type
Default: P
ALTYP2 P
Process Alarm
ALTYP2 D
Deviation Alarm
Selects alarms as latching or non-latching. Latching remains energized until you manually clear it.
This parameter will not appear if DIP switch
#7
is ON.
Range:
LAT
or
NLAT
Default:
NLAT
Allows the operator to change the input gain of the
RTD
Input for diierent curves. This parameter
will not appear if the input type is not RTD whole or RTD tenths, or DIP switch
#7
is ON.
Range:
JIS
or DIN
Default:
JIS
Selects the minimum percent of power that the
Series
920 will output. This parameter will not
appear if DIP switch
#7
is
ON,
Range: 0 to
100%
Default: 0
Selects
the
maximum percent of power that the
Series
920 will output. This parameter will not
appear
if DIP switch
#7
is ON.
Range: 0 to 100%
Default: 100
The Guaranteed Soak parameter guarantees the actual temperature is being controlled within a
window around set point.
lf
exceeded, the step time clock stops and the HOLD LED flashes until
the actual temperature is within the soak window.
Range: 0 to
90°F/
to
50°C
Default: 0
Represents the selection of the protocol type for serial communications. This selects
XON/XOFF
protocol or ANSI X3.28 communication protocol. This parameter will not appear if your Series 920
does not have communications.
Range: STX or XON
Default: STX
Represents the device identification number as required for the ANSI X3.28 communications
protocol for the Series 920. This parameter will not appear if
COM
has been selected as
XON,
or if
your Series 920 does not have communications.
Refer
to the 920 Data Communications Manual.
Range: 0 to 9
Default: 0
Allows for specific groups of parameters to be unaffected by the UP/DOWN and ENTER keys,
preventing these parameters from being changed accidentally.
0
=
No lock, full access of all parameters.
1
=
Prevents user from editing all parameters except the SYSTEM parameter group, the LOCK
parameter, the STEP and FILE parameter in the PROGRAM and
pre-RUN
groups.
2 -Prevents user from editing all parameters except
ER1
,
ER2,
&
ALRM
in the SYSTEM menu,
and the LOCK, STEP and FILE parameter are in the PROGRAM and
pre-RUN
menus.
Range: 0
-
2
Default: 0
Allows the operator to clear a file of the Series 920.Press ENTER, and choose the FILE? to clear.
Range:
1
-
10
Default:
1
From RETURN, you can go back to the SYSTEM prompt by pressing the ENTER key, or return to
SPCLFUNC by pressing the MODE key.
48
WATLOW
Series
920 User’s Manual
How To
Proqram
the Series
920,
Chapter 6