Ariens Path-Pro 136E User Manual Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
One of three main
level
operating menus.
From the SETUP menu, you can setup or
change system-operating parameters such as
real
time,
high/low
range, alarm types,
alarm points,
PID
settings
and communications.
You must select each ACCESS
number to create the personality of your Series
920.
1
ACCESS
(0)
1
ACCESS number (0) must be selected to enter the personality of your Series 920 into
the
CALIB
parameters.
CALIB
1
1
Tl
00:00
1
In the Series 920, when ACCESS (0) is entered under the SETUP menu, the
CALIB
parameters appear. These parameters set up the Real Time clock, alarms, and the
calibration offset of the process variable.
Represents the
current
Real Time hours and minutes of the Series 920s System.
Midnight
=
0 hours and 0 minutes. A Read Only parameter.
Represents the SYSTEM 24 hour time-ofday
clock
for hours.
Midnight
=
0 hours.
Range: 0
-
23 hours
Default: 0
The SYSTEM 24 hour
time-of-day
clock setting for minutes.
Range: 0 - 59 minutes Default: 0
1
CAL
()
An offset of the process variable. This number is added to the value that the system
derives. The final result is used for the control
point.
Range: -50 to
50°C/-90
to
9O°F
Default: 0
The Series 920 will display this parameter
represetin9
the high process alarm or high
deviation alarm for Alarm
1.
Displayed only when AUX 1
=
AL. See Page 43.
This parameter represents the low process alarm or low deviation alarm for Alarm 1 of
the Series 920. Displayed only when AUX1
=
AL
See Page 43.
Represents the high process alarm or high deviation alarm for Alarm 2 of the Series
920. Displayed only when
AUX2
=
AL. See Page 43.
The low process
alarm
or low deviation alarm for
Alarm
2 of the
Series
920.
Displayed
only when AUX2
=
AL. See Page 43.
From RETURN, you can go back to the SYSTEM prompt by pressing the ENTER key,
or return to ACCESS (0) menu by pressing the MODE key.
In the SETUP menu, ACCESS (1) must be selected to enter the
PID
parameters.
When ACCESS (1) is entered under the SETUP menu of the Series 920, the
PID
parameters will appear. These parameters consist of
Proportional,
Integral (auto
reset), and Derivative (rate) actions.
A proportional temperature band expressed in degrees within which a temperature
controller proportioning function is active for heating. Expressed in degrees. This
parameter will not appear if OUT
=
CL.
Range: 0 to
900°F/0
to
500°C
Default:
45°F/25°C
A reset (integral) heating control action that
automatically
eliminates offset, or “droop”,
between set point and actual process
temperature
in
a proportional control. Expressed
by repeats per minute. This parameter isn’t displayed if OUT
=
CL, or PB H is set to 0.
Range: 0.00 to 5.00 repeats/minute
Default: 0.00
The rate (derivative) heating function of the Series
920.
The rate is determined by how
fast the error being corrected is increasing.
Expressed in minutes. This parameter will
not appear if OUT=CL, or PBH=0.
Range: 0.00 to 5.00 minutes
Default: 0.00
How To Program the Series 920, Chapter 6
WATLOW
Series
920 User’s Manual 45
45